Zoom image

GreenMaster-HP

Exhaust Air Heat Pumps

GreenMaster-HP is an innovative product that can help properties meet the upcoming energy conservation requirements from Boverket. Heat recovery from exhaust air is an efficient and environmentally friendly solution for reducing energy consumption in properties.

By collaborating with NIBE and using high-quality ventilation units from AirSite, GreenMaster-HP is a reliable and efficient energy-saving solution. It is also noteworthy that the product has good aerodynamic properties and low noise levels, which can enhance the comfort of the residents in the property.

• High-temperature range:
• Supply air temperature up to 65°C
• Return air temperature up to 58°C
• Airflow 0.2–2.2 m³/s.
• Easy removal of the cooling module.
• Fire damper function to prevent smoke gases from entering the entire unit.

Dimensions, GreenMaster-HP

Zoom image

Integrated exhaust air unit and heat pump

GreenMaster-HP Compact


2

3

4

5

B

910

1010

1410

1710

H

1524

1632

1772

1824

H1

612

720

860

912

L

2000

2200

2200

2200

L1

600

700

600

600

L2

800

800

800

800

L3

600

700

800

800

L4

750

750

750

750

L5

700

700

700

700

L6

550

750

750

750

aB

750

800

1200

1500

aH

400

500

600

700

FidB

700

800

1200

1500

FidL

200

200

200

200

Data for additional options can be found in the GreenMaster Application AHU Selection Software.


Choosing the correct size of GreenMaster-HP


Living area (m²)¹

Airflow (l/s)

Heat pumps section

Cooling capacity exhaust (kW)

Energy consumption before the switch to HP (kWh)²

Annual COP at 55°C

CO₂ savings (kg/year)

GM-HP-2

860

400

GM-HP-12

9

123 885

4,1

4721

1070

500

GM-HP-16

11

154 138

3,9

5793

GM-HP-3


1290

600

GM-HP-16

13

185 829

3,9

6869

1500

700

GM-HP-12-12

15

216 080

4,0

7826

1710

800

GM-HP-16-12

18

246 331

3,9

9311

1930

900

GM-HP-16-15

19

278 023

4,0

9971

GM-HP-4


1930

900

GM-HP-16-12

22

278 023

3,9

11 203

2140

1000

GM-HP-16-15

24

308 275

4,0

12 274

2360

1100

GM-HP-16-20

27

339 966

3,8

13 411

2790

1300

GM-HP-16-30

32

401 910

3,6

15 638

GM-HP-5

3210

1500

GM-HP-16-30

35

458 547

3,6

17 303

  1. Assuming 35 liters per second & apartment, and an average apartment area of 75 m²
  2. Design outdoor temperature for Gothenburg -16°C, House insulation level 1980-1989, Heating power 45W/m2, and hot water supplement of 1/5 of total heating power. Heating medium 55/45°C. Cooling medium (Brine) 1/5°C.

Flow diagram, example with dual compressors

Zoom image

Energy labeling