DeltaMaster 2 48EC
FreeCooling for Telecommunications Stations
DeltaMaster 48EC is a unique market solution for cooling telecommunications stations using the low impulse principle.
Contents
- Fan housing in unpainted magnelis (C5), (painted version available as an option)
- Sound insulation
- EC fan with external rotor motor
- 2 pcs of hose clamps, Ø 160 mm
- 2 pcs of ePM10 70%-160-1500 filter bags
- 1 outdoor sensor
Electrical data, fan unit
- Voltage 48 V DC
- Rated power 112 W
- Rated current 2,2 A
- Speed 2700 rpm
- Sound pressure level 50 dBA (10 m)
Fan unit, Air Flow, dimensions and weight
- 250 l/s at external pressure of 50 Pa and clean filters
- Approved ambient temperature -25°C…+60°C
- Weight 10 kg
- Cooling capacity at Δt 2K* = 2-3 kW
- Cooling capacity at Δt 5K* = 4-6 kW
Classifications according to IEC
- Fan motor: IP42
- Temperature sensor: Protection Class II
- Connectors: IP20
- DeltaManager: IP54
* Variations may occur depending on the site.